XGF New-energy Step-up Substation
Step-up / grid-connection package substation for PV plants and wind farms. Integrates HV switchgear, transformer and monitoring.

Step-up / grid-connection package substation for PV plants and wind farms. Integrates HV switchgear, transformer and monitoring.
A solar power plant substation must turn variable generation into a grid-compliant feed. This solar power plant substation integrates step-up transformation, MV switching and monitoring for PV and wind connection.
How this family is built
Step-up and grid-connection duty
The XGF type is the PV-plant and wind-farm variant: it steps the collector voltage up to the grid voltage and combines the HV switchgear, transformer and monitoring in one package. Unlike a steady municipal load, generation follows the resource, so the unit is specified for frequent load variation and for remote telemetry back to the plant control system.
EV-charging and other impulse loads
A distinct variant serves charging stations. Charging is an intermittent impulse load: random vehicle starts and stops create frequent current swings, harmonics and surges. For this duty the package adds reactive-power compensation, harmonic treatment, fast relay protection and a metering / communications module, with the LV outgoing circuits planned around individual charger feeders. Temperature control, dehumidification and anti-condensation are fitted as standard for outdoor operation.
General-purpose box comparison
A general outdoor prefabricated box, by contrast, steps 10 kV down to 0.4 kV for a relatively steady load — a park, a factory retrofit, street lighting or temporary site supply — with a conventional HV room, transformer room and LV room and standard metering, compensation and protection. Choose the charging-duty variant only where impulse loading and harmonics are present.
Common models
XGF-10/0.4-1250, XGF-35/0.4-2500
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Rated HV voltage | 10 kV or 35 kV, 3-phase, 50 Hz | GB/T 17467 |
| Rated LV voltage | 0.4 kV (inverter side, per SLD) | Per single-line diagram |
| Capacity | 1000 – 3150 kVA per array block, confirmed at quotation | PV/wind step-up practice |
| Integrated equipment | HV switchgear + step-up transformer + LV panel + monitoring | Scope of supply |
| Transformer | Oil-immersed or dry-type, ONAN / AN cooling | GB/T 1094 |
| LV connection | Busbar or cable, per inverter output | Per SLD |
| Mechanical & environment | ||
| Enclosure | Al-Zn coated steel cabin, IP54 | GB/T 4208 |
| Ambient temperature | −25 to +45 °C standard, −40 °C option | Outdoor PV/wind practice |
| Altitude | ≤ 1000 m standard, derating above | GB/T 17467 |
| Ventilation | Louvers + exhaust fan, filter option for dusty sites | Cabin design |
| Compliance & scope | ||
| Standards | GB/T 17467, GB/T 19964 (PV grid connection), GB/T 19963 (wind) | Nameplate basis |
| Grid-connection scope | Protection, metering and communication per utility requirement | Per project |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.