HV System

High-voltage switchgear cabinet — Package Substation
Primary Systems

HV System

High-voltage incoming and distribution: ring main units / MV switchgear, load switches, vacuum circuit breakers, HV fuses, surge arresters, CT, PT and FTU/DTU terminals.

Primary systemBOM-linkedEngineer-specified
High-voltage switchgear cabinet — Package Substation

High-voltage incoming and distribution: ring main units / MV switchgear, load switches, vacuum circuit breakers, HV fuses, surge arresters, CT, PT, live indicators and distribution automation terminals (FTU/DTU).

The MV switchgear panel selection sets the protection and fault level of the incoming feeder. Each MV switchgear panel here is chosen by voltage, current and breaking duty.

Role in the substation

What the HV section contains

The high-voltage section handles the incoming supply and its protection. It is built around a ring main unit or medium-voltage switchgear, together with load switches, vacuum circuit breakers, HV fuses, surge arresters, current and voltage transformers, live-line indicators and a distribution automation terminal (FTU/DTU) where remote control is required.

Ring main unit or withdrawable switchgear

For smaller capacities and standard ring or radial feeders, an SF6 or air-insulated ring main unit is the economical choice. Where the capacity is larger, there are many feeders, or breaker-based protection is specified, an armoured withdrawable cabinet such as the KYN28 type is used instead; the circuit breaker inside is a fitted element, selected by breaking capacity.

Protective coordination

A transformer feeder is commonly protected by a load switch in series with current-limiting fuses — the fuse clears an internal transformer fault while the switch handles load current and cable charging current. Arresters protect against overvoltage and CT/PT provide metering and protection signals. Coordinate the ratings against the system short-circuit level and the project single-line diagram.

Items in this system

HXGN-12 Ring Main Unit (Whole Cabinet) — Package Substation

HXGN-12 Ring Main Unit (Whole Cabinet)

Box-type SF6-insulated ring main unit supplied as a complete cabinet. Load switch, fuse, arrester, CT/PT and live indicator are integrated by the manufacturer; selected by connection scheme (incomer + transformer feeder loops).

Read more →
KYN28A-12 Withdrawable Switchgear (Whole Cabinet) — Package Substation

KYN28A-12 Withdrawable Switchgear (Whole Cabinet)

Armoured withdrawable switchgear – the alternative to ring main units for larger capacity, multi-feeder or breaker-protection schemes. Supplied complete; the VS1/VD4 breaker inside is a fitted element.

Read more →
FLN36-12 SF6 Load Break Switch — Package Substation

FLN36-12 SF6 Load Break Switch

SF6-insulated load break switch, the core switching element inside ring main units and HV incomers.

Read more →
VS1 Vacuum Circuit Breaker (12 kV) — Package Substation

VS1 Vacuum Circuit Breaker (12 kV)

Indoor AC vacuum circuit breaker, commonly the fitted breaker element inside KYN28-12. Brand grade is often specified by the buyer.

Read more →
XRNT-12 HV Current-limiting Fuse — Package Substation

XRNT-12 HV Current-limiting Fuse

12 kV current-limiting high-voltage fuse for transformer protection, used in series with the load break switch on the transformer HV side.

Read more →
HY5WS Metal-oxide Surge Arrester — Package Substation

HY5WS Metal-oxide Surge Arrester

HY5WS series metal-oxide surge arrester for overvoltage protection of distribution equipment.

Read more →
JDZ Voltage Transformer (PT) — Package Substation

JDZ Voltage Transformer (PT)

Voltage transformer for metering and voltage signal acquisition on the HV side.

Read more →
LZZBJ Current Transformer (CT) — Package Substation

LZZBJ Current Transformer (CT)

Current transformer with metering and protection windings; rating chosen by ratio.

Read more →

Frequently asked questions

QWhat information is needed to specify this item?
A

Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.

QAre the parameters on this page the final project values?
A

No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.

QWhat is included in the quotation?
A

The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.

QCan the item be adapted to a project drawing?
A

Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.

Need this quoted?

Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.

Request a quotation
Package Substation

Specialized in package substations, switchgear cabinets and distribution components for global B2B projects. Configuration and bill of materials are fixed against the single-line diagram; assembly, wiring and routine test follow that drawing.

6 / 10 / 35 kV · 100–3150 kVA · IP54+

© 2026 Package Substation. All rights reserved.PrivacyContactmanager@packagesubstation.com