Main Transformer (Dry-type / Oil-immersed / Amorphous)
Single BOM line for the transformer. The content page splits by type: dry-type (SCB10/11/12/13), oil-immersed (S11/S13) and amorphous-alloy (SH15). Cooling fan, temperature controller and gas relay ship complete with the unit.

Single BOM line for the transformer. The content page splits by type: dry-type (SCB10/11/12/13), oil-immersed (S11/S13) and amorphous-alloy (SH15). Cooling fan, temperature controller and gas relay ship complete with the unit.
This item is specified against the single-line diagram and the site conditions; the common models and the parameter table below are the working reference, not a catalogue selection.
Package Substation Transformer — what this item does
Types and loss level
The transformer line splits by construction: epoxy-cast dry-type (SCB), oil-immersed (S11/S13) and amorphous-alloy (SH15). Dry types are preferred where fire safety and humidity tolerance matter; oil types are economical at higher ratings; amorphous cores cut no-load loss for lightly loaded, long-running sites.
Common models
SCB13-800/10 (dry-type), SCB13-1000/10 (dry-type), S13-M-800/10 (oil-immersed), SH15-M-630/10 (amorphous)
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Rated capacity | 315 – 1250 kVA typical | Distribution transformer range |
| HV winding | 10 / 6 kV, ±5 % or ±2 × 2.5 % tapping | SGB11 datasheet |
| LV winding | 0.4 kV | SGB11 datasheet |
| Vector group | Dyn11 | SGB11 datasheet |
| Frequency | 50 Hz | GB/T 1094 |
| Cooling | AN / AF (dry-type), ONAN (oil-immersed) | GB/T 1094 |
| Insulation class | F or H (dry-type) | H-class dry-type product line |
| Mechanical & environment | ||
| Noise, fans off | < 52 dB(A) at 2000 kVA (dry-type) | Dry-type technical requirement |
| Partial discharge | < 10 pC | Tianjin Zhongtuo 35 kV dry-type |
| Overload capability | 50 % continuous overload with fans running | Dry-type technical requirement |
| Ambient temperature | −30 to +40 °C | SGB11 datasheet |
| Altitude | ≤ 1000 m without derating | SGB11 datasheet |
| Amorphous option | Efficiency ≥ 97 % at rated load, 2 – 3 points above CRGO | BJBEB amorphous note |
| Compliance & scope | ||
| Loss basis | No-load and load loss per GB/T 6451 / GB 20052 limits | Nameplate basis |
| Standards | GB/T 1094, GB/T 6451, GB 20052, IEC 60076 | Nameplate basis |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.
Need this quoted?
Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.