Capacitor Compensation Cabinet (Whole Cabinet)
Automatic reactive-power compensation cabinet supplied complete by the compensation manufacturer – capacitors, reactor and controller are integrated.

Automatic reactive-power compensation cabinet supplied complete by the compensation manufacturer – capacitors, reactor and controller are integrated.
This item is specified against the single-line diagram and the site conditions; the common models and the parameter table below are the working reference, not a catalogue selection.
Compact Substation Components — what this item does
Why these are bought as complete assemblies
Whole assemblies — the cabin, transformer, ring main unit, withdrawable switchgear, LV board and compensation cabinet — are procured as complete, factory-tested objects rather than as loose parts. The manufacturer integrates the internal devices and issues the type-test and routine-test documentation, which keeps responsibility with one supplier and shortens site assembly.
What to check on a complete assembly
Confirm the rated voltage and current, the short-circuit withstand, the protection degree, the applicable standard and the interface drawing. For the transformer, state the winding type, loss level and vector group; for switchgear, state the breaking capacity and the operating mechanism.
Common models
GGJ (LV reactive compensation cabinet), BSMJ0.4-30-3 self-healing capacitor, JKW5C power factor controller
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Rated voltage | 400 V (LV) / 10 kV (HV) | GGJ datasheet |
| Step size | 30 kvar per step (BSMJ0.4-30-3) | BSMJ model code |
| Total capacity | Per compensation scheme | Per SLD |
| Series reactor | 7 % typical, tuned to the dominant harmonic | Detuned compensation practice |
| Controller | JKW5C power-factor controller, steps per scheme | GGJ datasheet |
| Switching | Capacitor-duty contactors with damping reactors | Product design |
| Mechanical & environment | ||
| Discharge | Discharge resistors, ≤ 50 V within 3 min after disconnection | GB/T 12747 |
| Ingress protection | IP30 indoor cabinet | GB/T 4208 |
| Ambient temperature | −5 to +40 °C, ventilated | GB/T 7251.1 |
| Mounting | Floor-standing cabinet, front access | Product design |
| Compliance & scope | ||
| Standards | GB/T 3984, GB/T 12747, IEC 60831 | Nameplate basis |
| Typical use | Reactive-power compensation at the LV main busbar | Product scope |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.
Need this quoted?
Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.