European-style prefabricated substation with separate HV, transformer and LV compartments. Convenient for maintenance, widely used in urban distribution.

European-style prefabricated substation with separate HV, transformer and LV compartments. Convenient for maintenance, widely used in urban distribution.
The box type substation shown here is the European-style, three-compartment product in this range. This box type substation keeps HV, transformer and LV accessible separately, which is the reason it is specified for continuity-sensitive sites. In practice that is what a compact substation design has to deliver: three functions, one enclosure, and a maintenance route into each function without opening the other two.
How this family is built
European layout and compartmentation
The YB type follows the European-style prefabricated arrangement: the high-voltage incoming section, the transformer and the low-voltage distribution board occupy separate compartments inside one enclosure. Keeping the three functions apart is the main maintenance advantage of this layout — the switchgear and the transformer can be inspected independently, and a fault in one compartment does not force work on the others. This is why the European configuration is normally chosen for urban distribution and commercial sites where continuity of supply and safe access matter.
How the unit is built and commissioned
The assembly is prefabricated and routinely tested in the factory, transported as a complete unit and lowered onto a prepared foundation. Site work is reduced to the base, the cable terminations and final commissioning, which shortens the programme compared with a conventional brick-built distribution room. Protection is typically IP54 or above — dustproof and rainproof for outdoor service — with natural and forced ventilation and anti-condensation heaters specified for humid climates.
Selection points
Confirm the HV rating (commonly 10 kV or 6 kV), LV rating (0.4 kV), transformer capacity in kVA, the incoming scheme (ring, dual-source or terminal) and the short-circuit level before ordering. Type-test reports to GB/T 17467 and IEC 62271-202 should be checked against the project specification.
Common models
YB-12/0.4-630, YB-10/0.4-400, YBM(P)12-12/0.4-800
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Rated HV voltage | 10 kV or 6 kV, 3-phase, 50 Hz | GB/T 156; GB/T 17467 |
| Rated LV voltage | 0.4 kV (400/230 V) | GB/T 156 |
| Transformer capacity | 100 – 1600 kVA, per SLD | YB series range |
| HV side | Ring main unit or KYN28-type switchgear, 12 kV, 630 A | Per single-line diagram |
| LV side | Main busbar sized to transformer rating, to 1600 A | Per transformer rating |
| Compartment layout | HV / transformer / LV, three separate compartments | GB/T 17467 |
| Mechanical & environment | ||
| Enclosure | Al-Zn coated steel 1.5 – 2.5 mm, stainless or GRC option | Fabricator shell range |
| Ingress protection | IP54 as standard, IP54+ on request | GB/T 4208 |
| Ambient temperature | −35 to +40 °C | YB official datasheet, same enclosure family |
| Altitude | ≤ 1000 m without derating | YB official datasheet |
| Relative humidity | Daily mean ≤ 95 %, monthly mean ≤ 90 % | YB official datasheet |
| Site slope | Ground slope ≤ 3° | ZGS installation condition |
| Compliance & scope | ||
| Standards | GB/T 17467-1998, DL/T 537-93, IEC 62271-202 | Nameplate basis |
| Scope of supply | Cabin, HV/LV switchgear, transformer, wiring, lighting, earthing | Per BOM |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.
Related systems and items
The five functional systems show what this family is assembled from; send the diagram for a project BOM.
Need this quoted?
Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.