Motor Drive & Distribution Automation Terminal (FTU/DTU)
Electric spring operating mechanism plus FTU/DTU telecontrol terminal for smart ring main units and distribution automation retrofits – a growing segment.

Electric spring operating mechanism plus FTU/DTU telecontrol terminal for smart ring main units and distribution automation retrofits – a growing segment.
The automation & drive group turns a manual ring main unit into a remotely controlled node with telemetry and switching commands.
This item is specified against the single-line diagram and the site conditions; the common models and the parameter table below are the working reference, not a catalogue selection.
Kiosk Substation Components — what this item does
Remote control of the MV network
Motor drives and FTU/DTU terminals turn a manual ring main unit into a remotely controlled node: telemetry, fault indication and switching commands are exchanged with the distribution control centre, commonly over IEC 60870-5-104.
Common models
FTU (feeder terminal unit), DTU (distribution terminal unit), Spring operating mechanism (CT10 / CD10)
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Devices | FTU feeder terminal, DTU distribution terminal | Product scope |
| Protocols | IEC 60870-5-101 / -104, Modbus RTU | DL/T 634.5104 |
| Communication | Fibre, Ethernet or 4G, per utility requirement | Per project |
| Power supply | 24 / 48 V DC, or AC/DC 220 V | Product variant |
| Inputs / outputs | 3 × CT, 3 × PT, 8 – 16 DI, 4 – 8 DO, per scheme | Per scheme |
| Mechanism drive | Spring operating mechanism (CT10 / CD10) retrofit | Product scope |
| Mechanical & environment | ||
| Enclosure | IP54 outdoor cabinet for the FTU, panel-mount for the DTU | GB/T 4208 |
| Ambient temperature | −40 to +70 °C, industrial grade | Outdoor automation practice |
| Compliance & scope | ||
| Standards | DL/T 634.5101, DL/T 634.5104, DL/T 721 | Nameplate basis |
| Typical use | Smart RMU, feeder automation and DA retrofit | Product scope |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.
Need this quoted?
Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.