KYN28A-12 Withdrawable Switchgear (Whole Cabinet)
Armoured withdrawable switchgear – the alternative to ring main units for larger capacity, multi-feeder or breaker-protection schemes. Supplied complete; the VS1/VD4 breaker inside is a fitted element.

Armoured withdrawable switchgear – the alternative to ring main units for larger capacity, multi-feeder or breaker-protection schemes. Supplied complete; the VS1/VD4 breaker inside is a fitted element.
This MV switchgear is an armoured withdrawable cabinet; the breaker can be racked out for maintenance without isolating the busbar.
This item is specified against the single-line diagram and the site conditions; the common models and the parameter table below are the working reference, not a catalogue selection.
MV Switchgear Panel — what this item does
Withdrawable breaker switchgear
KYN28 is an armoured, metal-enclosed withdrawable cabinet. The breaker can be racked out for maintenance without disconnecting the busbar, which improves availability. It is chosen by rated current and breaking capacity for incomer and feeder duties.
Common models
KYN28A-12/630-25, KYN28A-12/1250-31.5, KYN28A-12/1600-40
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Rated voltage | 12 kV | KYN28A-12 datasheet |
| Rated current | 630 / 1250 / 1600 A | KYN28A-12 model code |
| Rated breaking current | 25 / 31.5 / 40 kA | KYN28A-12 model code |
| Short-time withstand | 25 / 31.5 / 40 kA, 4 s | GB/T 11022 |
| Power-frequency withstand | 42 kV / 1 min | GB/T 11022 |
| Lightning impulse withstand | 75 kV | GB/T 11022 |
| Busbar rating | 630 – 1600 A, copper, heat-shrink sleeved | Per SLD |
| Mechanical & environment | ||
| Construction | Armoured, metal-enclosed, withdrawable truck | GB/T 3906 |
| Compartment segregation | Breaker / busbar / cable / relay, separate | Product design |
| Ingress protection | IP4X shell, IP2X between compartments | GB/T 4208 |
| Ambient temperature | −25 to +40 °C | GB/T 11022 |
| Altitude | ≤ 1000 m without derating | GB/T 11022 |
| Compliance & scope | ||
| Standards | GB/T 11022, GB/T 3906, IEC 62271-200 | Nameplate basis |
| Typical use | 10(6) kV incomer and feeder, multi-feeder schemes | Product scope |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.
Need this quoted?
Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.