HXGN-12 Ring Main Unit (Whole Cabinet)
Box-type SF6-insulated ring main unit supplied as a complete cabinet. Load switch, fuse, arrester, CT/PT and live indicator are integrated by the manufacturer; selected by connection scheme (incomer + transformer feeder loops).

Box-type SF6-insulated ring main unit supplied as a complete cabinet. Load switch, fuse, arrester, CT/PT and live indicator are integrated by the manufacturer; selected by connection scheme (incomer + transformer feeder loops).
This item is specified against the single-line diagram and the site conditions; the common models and the parameter table below are the working reference, not a catalogue selection.
RMU Ring Main Unit Types — what this item does
Where a ring main unit fits
A ring main unit is the compact MV solution for ring and radial distribution: load switch, fuse, arrester and indicators are integrated in a sealed cabinet. It is selected by connection scheme and fault level; use a withdrawable breaker cabinet instead where there are many feeders or breaker-only protection is required.
Common models
HXGN15-12/630 (SF6 RMU), HXGN15-12/1250-31.5, HXGN-12F (air-insulated), XGN15-12
Typical parameters
| Parameter | Typical value | Basis |
|---|---|---|
| Electrical | ||
| Rated voltage | 12 kV | HXGN-12 datasheet |
| Rated current | 630 A (1250 A variant) | HXGN-12 datasheet |
| Rated breaking current | 20 kA | HXGN-12 datasheet |
| Short-time withstand | 20 kA / 4 s | GB/T 3906 |
| Power-frequency withstand | 42 kV / 1 min | GB/T 11022 |
| Lightning impulse withstand | 75 kV | GB/T 11022 |
| Busbar rating | 630 A, copper | Per SLD |
| Mechanical & environment | ||
| Insulation medium | SF6 (HXGN15) or air (HXGN-12F) | Product variant |
| Operating mechanism | Manual spring, motorised option | Product variant |
| Ingress protection | IP3X indoor, IP54 with outdoor enclosure | GB/T 4208 |
| Ambient temperature | −25 to +40 °C | GB/T 3906 |
| Altitude | ≤ 1000 m without derating | GB/T 11022 |
| Compliance & scope | ||
| Standards | GB/T 3906, GB/T 11022, IEC 62271-200 | Nameplate basis |
| Typical use | Ring network, urban and industrial distribution | Product scope |
Values are the working reference for this family and its standard models. On a project the rating, protection and cable schedule are confirmed against the single-line diagram and the site conditions before the quotation is issued.
Frequently asked questions
QWhat information is needed to specify this item?
Send the single-line diagram, rated voltage and current or capacity, short-circuit duty, installation environment, cable or terminal schedule, and any interface dimensions that apply to the item.
QAre the parameters on this page the final project values?
No. They are working reference values for the product family. The final model, rating, protection, accessories and scope are confirmed against the single-line diagram and site conditions before quotation.
QWhat is included in the quotation?
The quotation identifies the selected configuration, bill of materials, scope of supply and applicable test or document package. Loose accessories and site work are listed separately when applicable.
QCan the item be adapted to a project drawing?
Project-specific dimensions, interfaces and accessories can be reviewed against the drawings. Feasibility and the final configuration are confirmed for the selected model before production.
Need this quoted?
Send the single-line diagram and the site conditions. You get back a configuration, a bill of materials and a scope of supply — in writing, at quotation.